Notifier AFP-2800 Operation, Installation & Programming Manual page 81

Intelligent, analogue addressable panel with non-proprietary programming tools
Hide thumbs Also See for AFP-2800:
Table of Contents

Advertisement

6.3.8.2
S
ERVICE
Performs a test of Database RAM, this will clear all database information etc. The system will take several
seconds to re-acquire all system information but will not destroy any configuration information.
6.3.8.3
S
ERVICE
This will perform a full CRC check (up to 30 seconds) on the Flash memory to confirm correct operation.
6.3.8.4
S
ERVICE
This mode will test the correct operation of local relays by cycling through them one at a time. Pressing any button
stops the test.
6.3.8.5
S
ERVICE
This mode will test the correct operation of expansion relays within the panel by cycling through them one at a
time. Pressing any button stops the test.
6.3.8.6
S
ERVICE
This mode will test the correct operation of panel LED and LCD display by randomly flashing LEDS and filling the
LCD with data. Pressing any button stops the test.
6.3.8.7
S
ERVICE
This mode will perform tests on field modules to ensure correct communications and operation.
MODULE TEST MENU
DAY MODE
20 JULY 2002 14:44:37
1) AZF . . . . AUTOTEST ALL AZFS ON MODULE
2) DOUT . . . .AUTOTEST ALL Dig. OUTS ON MODULE
3) DBASE . . . DISPLAY MODULE DBASE
USE UP/DOWN BUTTONS TO SELECT A FUNCTION
UP
DOWN
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
M
– D
ENU
IAGNOSTICS
M
– D
ENU
IAGNOSTICS
M
– D
ENU
IAGNOSTICS
M
– D
ENU
IAGNOSTICS
M
– D
ENU
IAGNOSTICS
M
– D
ENU
IAGNOSTICS
A = 0
F = 0
I = 0
N = 1
SELECT
BACK
– D
BASE
– F
LASH
– R
ELAY
– XR
ELAY
– LED
– M
ODULE
Actions:
Use the UP and DOWN buttons to scroll through
options and then use the SELECT button to
select the highlighted option
(or button 1 to 3 from the numeric keypad)
Press the BACK button to return to the Service
Menu screen.