6.3.5.2
S
ERVICE
Overview:
This Config menu is used for adding and removing distributed field modules from the RS485 ring. Even though
the AFP-2800/2802 auto-detects any new modules and adds them to the system approximately every 5 minutes.
You may have a module that is not physically installed yet, but you wish to configure its inputs etc. You can use
this menu to add the module to the system. If the module is not physically found the panel will register a fault but it
will still allow you to set all the parameters.
Similarly, if a module had been physically removed from the system, you can use this menu item to permanently
remove it from the panel's memory.
How to Add/Remove modules
ADD/ REMOVE MODULE
DAY MODE
20 JULY 2002 14:44:37
USE BUTTONS TO SELECT A MODULE:
MODULES FOUND ON RING 1:
001 002 003 004 005 006 007 101 102 103
USE UP/DOWN BUTTONS TO SELECT A RING:
PREV
NEXT
AFP-2800/2802 Manual – P/N 11249 11-Mar-08
M
– C
ENU
ONFIG
A = 0
F = 0
I = 0
N = 0
BACK
ADD
REMOVE
– M
(A
/ R
ODULE
DD
Actions:
To remove a module:
Use the PREV and NEXT buttons to scroll
through the list of active modules. Once the desired
module is selected, press the REMOVE button
once to remove it.
To Add a module:
Press the ADD button once.
You will be prompted to enter a module number to
add.
Then you will be prompted for a module type from
the on screen list of 1-8 i.e. (FANC,AZM8,
ACM16AT,ACM32,SCS8, LDM32, LCD80)
The module has now been added.