Switching HART
Some systems are not capable of communicating with HART Revision 7 devices. The
following procedures list how to change HART revisions between HART Revision 7 and
HART Revision 5.
5.7.1
Switch HART
If the HART configuration tool is not capable of communicating with a HART Revision 7
device, it should load a generic menu with limited capability. The following procedures
allow for switching between HART Revision 7 and HART Revision 5 from a generic menu.
Procedure
1. To change to HART Revision 5, enter HART5 in the Message field.
2. To change to HART Revision 7, enter HART7 in the Message field.
5.7.2
Switch HART
Procedure
From the HOME screen, enter the Fast Key sequence and follow steps within the Field
Communicator to complete the HART revision change.
Device Dashboard Fast Keys
5.7.3
Switch HART
Procedure
1. Select Manual Setup and select HART.
2. Select Change HART Revision; then follow the on screen prompts.
5.7.4
Switch HART
Procedure
Navigate to HART REV within the extended menu and select either HART REV 5 or HART
REV 7. Use
Rosemount 3051P
®
revision with generic menu
®
revision with Field Communicator
®
revision with AMS Device Manager
Note
AMS Device Manager versions 10.5 or greater are compatible with HART Revision 7.
®
revision with local operator interface (LOI)
Figure 5-8
to change HART Revision.
®
revision
HART5
2, 2, 5, 2, 4
Operation and maintenance
April 2020
HART7
2, 2, 5, 2, 3