Section 2: Configuration
March 2014
Damping with AMS Device Manager
1.
Right click on the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a local operator interface
Reference
Figure 2-9. Damping with LOI
2.7

Configuring the LCD display

The LCD display configuration command allows customization of the LCD display to suit
application requirements. The LCD display will alternate between the selected items.
In the following instructions, the LCD display can also be configured to display configuration
information during the device startup. Select Review Parameters at Startup to enable or
disable this functionality.
Reference
display screen.
18
Figure 2-9
to enter damping values using an LOI.
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Pressure Units
Sensor Temperature
% of Range
mA/Vdc Output
Scaled Variable
Figure 1-2 on page 5
EXTENDED MENU
CALIBRAT
DAMPING
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
LCD display with Local Operator Interface for image of LCD
Reference Manual
00809-0100-4108, Rev BA
Configuration