4.2 Connecting an External Rectifier
The external rectifier supplies power to IP phones or a WBS24 when a PLIM module is
used. The internal power source has insufficient capacity.
The procedure to connect an external rectifier is as follows:
1) Switch off the power to the OfficeServ 7400 and external rectifier.
2) There are three screws to connect the power cable (Figure 4.2) to connectors A and B
(GND and -54 V) on the rear panel of the external rectifier (Figure 4.3)
The power cable comprises a red and a blue line and the ends of the lines are marked
GND (red), and -48VDC (blue).
Loosen the screws and connect the power cable as shown in Figure 4.3. Connect the
red line to A (GND) and the blue line to B (-54V) on the rear of the external rectifier
and tighten the screws.
A
B
© Samsung Business Communications
Figure 4.2 Power Cable
Red Line
Figure 4.3 Connecting an External Rectifier
OfficeServ 7400 Installation Guide
Button for external battery
Blue Line
External Battery Socket
External
Rectifier
OfficeServ
7400
4-3