WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 is used for the fuctional block, then Input 2 have to be used for
the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
sensor. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the sensor. This test is
performed by occupying and clearing the area protected by the sensor to run a complete
function test and enable the output. This test is only requested at machine start-up (when
the unit is switched on).
Filter (ms): This is used to filter the signals coming from the sensor. The filter can be
configured to between 3 and 250 ms and eliminates any bouncing on the contacts. The
length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
68
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25th June 2012 • Rev.15