Reer MOSAIC Master M1 Installation And Use Manual page 17

Modular safety integrated controller
Hide thumbs Also See for MOSAIC Master M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
TERMINAL
SIGNAL
1
24VDC
2
NODE_SEL0
3
NODE_SEL1
4
GND
5
OSSD1_A
6
OSSD1_B
7
RESTART_FBK1
8
OUT_STATUS1 Output Programmable digital output
9
OSSD2_A
10
OSSD2_B
11
RESTART_FBK2
12
OUT_STATUS2 Output Programmable digital output
13
24VDC
14
24VDC
15
GND
16
GND
17
OSSD4_A
18
OSSD4_B
19
RESTART_FBK4
20
OUT_STATUS4 Output Programmable digital output
21
OSSD3_A
22
OSSD3_B
23
RESTART_FBK3
24
OUT_STATUS3 Output Programmable digital output
TERMINAL
SIGNAL
1
24VDC
2
NODE_SEL0
3
NODE_SEL1
4
GND
5
OSSD1_A
6
OSSD1_B
7
RESTART_FBK1
8
OUT_STATUS1
9
OSSD2_A
10
OSSD2_B
11
RESTART_FBK2
12
OUT_STATUS2
13
24VDC
14
n.c.
15
GND
16
n.c.
8540780 • 25th June 2012 • Rev.15
MO4
TYPE
DESCRIPTION
-
24VDC power supply
Input
Node selection
Input
-
0VDC power supply
Output
Static output 1
Output
Input
Feedback/Restart 1
Output
Static output 2
Output
Input
Feedback/Restart 2
-
24VDC power supply
-
24VDC power supply
-
0VDC power supply
-
0VDC power supply
Output
Static output 4
Output
Input
Feedback/Restart 4
Output
Static output 3
Output
Input
Feedback/Restart 3
Table 6
MO2
TYPE
DESCRIPTION
-
24VDC power supply
Input
Node selection
Input
-
0VDC power supply
Output
Static output 1
Output
Input
Feedback/Restart 1
Output Condition of outputs 1A/1B
Output
Static output 2
Output
Input
Feedback/Restart 2
Output Condition of outputs 2A/2B
-
24VDC power supply
-
-
-
0VDC power supply
-
-
Table 7
OPERATION
-
Input
("type B" according to EN 61131-2 )
Input
("type B" according to EN 61131-2 )
-
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
OSSD1/2 power supply
OSSD3/4 power supply
-
-
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
OPERATION
-
Input
("type B" according to EN 61131-2 )
Input
("type B" according to EN 61131-2 )
-
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
OSSD1/2 power supply
-
-
-
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents