Monitored. When Manual is selected the system only verifies the signal's transition from 0
to 1. If Monitored is selected the double transition from 0 to 1 and then back to 0 is
verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 is used for the fuctional block, then Input 2 have to be used for
the Reset Input.
Output test: This is used to select which test output are to be sent to the photocell test
input. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by occupying and clearing the photocell to run a complete function
test and enable the output. This test is only requested at machine start-up (when the unit
is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.