Mapping of DetailedQuality

The value of DetailQuality is mapped to a DetailedQuality bitmap.
Table 3.2.4-1 Mapping of DetailedQuality
Name
overflow
outOfRange
badReference
oscillatory
failure
oldData
inconsistent
inaccurate
Example:
DetailQuality = 1d = 00000001b > overflow = true
DetailQuality = 16d = 00010000b > failure = true

Analogue value (AnalogueValue)

Analogue values are always presented as 32-bit float values (VT_R4) so that the .f and
.i extensions are discarded from the attribute names to simplify the OPC namespace. If
a device only supports integer values, the value is converted to a floating point present-
ation of the value according to its configuration and the following formula, refer to
3.2.6, Configuration of analogue value (ScaledValueConfig).
Type
Value/ Value
range
FALSE (0) |
TRUE (1)
FALSE (0) |
TRUE (1)
Type
Value/ Value
range
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1MRS758690
M/O/C
OPC Data Type
M
VT_BOOL
M
VT_BOOL
M/O/C
Bit
M
0
M
1
M
2
M
3
M
4
M
5
M
6
M
7