Controllable Integer Status (Inc) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

1MRS758690
3.2.17.3.
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual

Controllable integer status (INC)

The following table defines the common data class of controllable integer status.
Table 3.2.17.3-1 Controllable integer status (INC)
Name
Type
lastApplError
ApplicationErr-
orCode
ctlVal
INT32
operTm
TimeStamp
orCat
ENUMER-
ATED
orIdent
OCTET
STRING64
ctlNum
INT8U
stVal
INT32
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
INT32
subQ
Quality
subID
VISIBLE
STRING64
ctlModel
ENUMER-
ATED
sboTimeout
INT32U
sboClass
ENUMER-
ATED
minVal
INT32
FC
Value/ Value
range
Refer to
3.2.22, Applica-
tion error
codes
CO
CO
CO, ST
0..255
ST
ST
ST
ST
FALSE |
TRUE
SV
SV
SV
SV
Text
CF
Status-only (0)
| direct-with-
normal-secur-
ity (1) | sbo-
with-normal-
security (2) |
direct-with-
enhanced-
security (3) |
sbo-with-
enhanced-
security (4)
CF
CF
operate-once
(0) | operate-
many (1)
CF
M/O
OPC Data
Type
VT_I4
M
VT_I4
O
VT_DATE
O
VT_I4
O
VT_BSTR
O
VT_I4
M
VT_I4
M
VT_I4
M
VT_DATE
O
VT_BOOL
O
VT_BOOL
O
VT_I4
O
VT_I4
O
VT_BSTR
M
VT_I4
O
VT_I4
O
VT_I4
O
VT_I4