ABB COM600 series 5.0 Technical Reference Manual page 68

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

68
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Name
Value or Value range/ Default
Diagnostic events
0 = Disabled
level
1 = Level1 (main operation,
error replies, errors)
2 = Level2 (+ Information
Reports, OK replies, RCB init)
3 = Level3 (+ sent requests
(connect,read,write), transpar-
ent SPA messages)
4 = Level4 (+ reported local
updates)
5 = Level5 (+ reported uncon-
figured updates)
IP address
0.0.0.0 - 255.255.255.255
Configuration ver-
Version information
sion
Transparent XSAT
Diagnostic coun-
ters
Sent connection
requests
Received connec-
tion replies ok
Received connec-
tion replies error
Description
Data Type: Integer
Access: No limitations
Sets diagnostics event level
Data type: Text
Access: Read-only (configuration)
IP address of the physical device
Data type: Text
Access: Read-only
The version information of the current
configuration for this device.
See 3.3.5, Transparent XSAT.
Data type: Integer
Access: No limitation
Connection requests sent to device
Data type: Integer
Access: No limitation
Success connection replies received from
device (connection accepted)
Data type: Integer
Access: No limitation
Failure connection replies received from
device (connection refused).
1MRS758690