Modbus And Snmp Mapping - ABB CMS-700 User Manual

Circuit monitoring system
Hide thumbs Also See for CMS-700:
Table of Contents

Advertisement

CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)

Modbus and SNMP Mapping

Modbus Standard TCP Port:
Standard SNMP Port:
Addr.
Addr.
Word
Description
(hex)
(dec)
(16-bit)
Ongoing measurement values:
These registers contain the actual measured data.
0000
0
1
TRMS value of Sensor 1
0001
1
1
TRMS value of Sensor 2
...
...
1
...
005F
95
1
TRMS value of Sensor 96
0100
256
1
AC value of Sensor 1
0101
257
1
AC value of Sensor 2
...
...
1
...
005F
351
1
AC value of Sensor 96
0200
512
1
DC value of Sensor 1
0201
513
1
DC value of Sensor 2
...
...
1
...
025F
607
1
DC value of Sensor 96
Minimum measured values:
These registers contain the minimum measured values since last system start / reset or since last "reset min/max values" request.
0400
1'024
1
TRMS min value of Sensor 1
0401
1'025
1
TRMS min value of Sensor 2
...
...
1
...
045F
1'119
1
TRMS min value of Sensor 96
0500
1'280
1
AC min value of Sensor 1
0501
1'281
1
AC min value of Sensor 2
...
...
1
...
055F
1'375
1
AC min value of Sensor 96
0600
1'536
1
DC min value of Sensor 1
0601
1'537
1
DC min value of Sensor 2
...
...
1
...
065F
1'631
1
DC min value of Sensor 96
Maximum measured values:
These registers contain the maximum measured values since last system start / reset or since last "reset min/max values" request.
0800
2'048
1
TRMS max value of Sensor 1
0801
2'049
1
TRMS max value of Sensor 2
...
...
1
...
085F
2'143
1
TRMS max value of Sensor 96
0900
2'304
1
AC max value of Sensor 1
0901
2'305
1
AC max value of Sensor 2
...
1
...
095F
2'399
1
AC max value of Sensor 96
0A00
2'560
1
DC max value of Sensor 1
0A01
2'561
1
DC max value of Sensor 2
...
...
1
...
0A5F
2'655
1
DC max value of Sensor 96
8001
8002
Resolution
Unit
Format
(1-bit value)
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
unsigned
0.01
A
signed
0.01
A
signed
0.01
A
signed
0.01
A
signed
Access
SNMP
Variable Name
R (03)
TRMSsens1
R (03)
TRMSsens2
R (03)
...
R (03)
TRMSsens96
R (03)
ACsens1
R (03)
ACsens2
R (03)
...
R (03)
ACsens96
R (03)
DCsens1
R (03)
DCsens2
R (03)
...
R (03)
DCsens96
R (03)
MINTRMSsens1
R (03)
MINTRMSsens2
R (03)
...
R (03)
MINTRMSsens96
R (03)
MINACsens1
R (03)
MINACsens2
R (03)
...
R (03)
MINACsens96
R (03)
MINDCsens1
R (03)
MINDCsens2
R (03)
...
R (03)
MINDCsens96
R (03)
MAXTRMSsens1
R (03)
MAXTRMSsens2
R (03)
...
R (03)
MAXTRMSsens96
R (03)
MAXACsens1
R (03)
MAXACsens2
R (03)
...
R (03)
MAXACsens96
R (03)
MAXDCsens1
R (03)
MAXDCsens2
R (03)
...
R (03)
MAXDCsens96
59