4.2.3.
Name
Type
stVal
ENUMERATED
q
Quality
t
TimeStamp
4.2.4.
Name
Type
stVal
INTEGER
q
Quality
t
TimeStamp
4.2.5.
Name
Type
stVal
ENUMERATED
q
Quality
t
Timestamp
d
Description
90
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual

Double point status (DPS)

DPS represents DMCD M_DP_NA_1, M_DP_TA_1, M_DP_TB_1.
Value/ Value
range
Intermediate-state
(0)
off (1)
on (2)
bad-state (3)

Integer status (INS)

Value/ Value
range

Enumerated Status (ENS)

Value/ Value
range
Text
ENS represents DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1
Mandat-
Protocol informa-
ory/Optional
tion element
M
DPI
M
BL, SB, NT, IV
M
CP24Time2a
CP56Time2a
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA, COI
M
OV, BL, SB, NT, IV
M
CP24Time2a
CP56Time2a
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA, COI
M
OV, BL, SB, NT, IV
M
CP24Time2a
CP56Time2a
O