Abbcommandbitmask - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.14.
30
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
starting with 30 December 1899, midnight as time zero. Hour values are expressed as
the absolute value of the fractional part of the number.

AbbCommandBitmask

The following table defines the mapping of AbbCommandBitmask. This ABB-specific
control value is a bitmask value of a command to a device. This value is applicable to
ABB extension control attributes.
Table 3.2.14-1 AbbCommandBitmask
Name
NormalControl
InterlockOverride
Synchrocheck-
Override
TestCommand
Originator
ControlValue
NormalControl: True = normal operation, false = inverse operation (for example, On
> Off).
InterlockOverride: True = interlockcheck > false
SynchrocheckOverride : True = syncrocheck > false
TestCommand: True = test command
Originator: Command originator (= Originator.orCat)
Type
Value/ Value
range
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
1bit
FALSE (0) |
TRUE (1)
4bit
not-supported(0)
| bay-control(1) |
station-control(2)
| remote-con-
trol(3) | automatic-
bay(4) | auto-
matic-station(5) |
automatic-
remote(6) | main-
tenance(7) | pro-
cess(8)
nbit
1MRS758690
M/O/C
Bit Position
M
0
M
1
M
2
M
3
M
4-7
M
8-31