Wye; Delta (Del) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.16.4.
3.2.16.5.
40
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual

WYE

The following table defines the common data class of WYE. This class is a collection
of simultaneous measurements of values in a three phase system that represent phase to
ground values.
Table 3.2.16.4-1 WYE
Name
Type
phsA
CMV
phsB
CMV
phsC
CMV
neut
CMV
net
CMV
res
CMV
angRef
ENUMER-
ATEDe
d
VISIBLE
STRING255
dU
UNICODE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
dataNs
VISIBLE
STRING255
a. One or more of these items (1 - 6) must be present.

Delta (DEL)

The following table defines the common data class of delta. This class is a collection of
measurements of values in a three phase system that represent phase to phase values.
FC
Value/ Value
range
MX
MX
MX
MX
MX
MX
CF
Va (0) | Vb (1)
| Vc (2) | Aa
(3) | Ab (4) |
Ac (5) | Vab
(6) | Vbc (7) |
Vca (8) |
Vother (9) |
Aother (10)
DC
Text
DC
EX
EX
EX
1MRS758690
M/O
OPC Data
Type
O
a
O
a
O
a
O
a
O
a
O
a
O
VT_I4
O
VT_BSTR
O
VT_BSTR
O
VT_BSTR
O
VT_BSTR
O
VT_BSTR