ABB COM600 series 5.0 Technical Reference Manual page 62

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

62
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Name
Value or Value range/ Default
Reset
By writing 1 the server is reset.
By writing 2 the log file is
cleared.
Other values are currently
ignored.
File version
Version information
Product version
Version information
Timesync client
In use
0 = Not in use
1 = In use
Default: 1
Timesync status
False = Not synchronised
True = Synchronised OK
Timesync server
Description
Data type: Integer
Access: No limitations
Makes it possible for clients to reset the
OPC server. A reset means that the server
disconnects all clients and reloads the
configuration file.
When the last client is discon-
nected the server usually shuts
down. The server does not shut
down if it was not started by the
COM runtime or if it is running
as a Windows service. In that
case the configuration file is not
reloaded.
Data type: Text
Access: Read-only
The file version number of the OPC
server/client exe file.
Data type: Text
Access: Read-only
The version (revision) of the package that
the server/client belong to.
Data type: Integer
Access: No limitations
Status of the integrated SNTP clients time
synchronization routine. Value is 0 when
not in use and 1 when in use. By writing
0 the client is started and by writing 1 it is
stopped. The client can be started only if
configuration parameters are given in a
configuration file.
Data type: Boolean
Access: Read-only
Status of the integrated SNTP client time
synchronization routine. Value is false
when synchronization is not received and
true when synchronization received and
local time set OK.
1MRS758690

Advertisement

Table of Contents
loading