ABB COM600 series 5.0 Technical Reference Manual page 67

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

1MRS758690
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Name
Value or Value range/ Default
Object status
94 = Init (checking configura-
tion version for single rcb)
95 = init (checking rcb attrib-
utes for single rcb)
96 = Init (reading rcb variable
list for single rcb)
97 = Init (enabling reporting for
single rcb)
98 = Init (rcb init ok for single
rcb)
100 = Ready
101 = Suspended (= not in use)
102 = Device simulated
86 = Report control block initial-
ization error (restarting rcb init)
88 = Configuration version error
(device is suspended)
89 = error (not specified)
90 = Device not connected
91 = Initializing
92 = Initializing rcb (after error
in reporting init or information
report flow)
93 = Reinitialize (after reconnec-
tion if init done)
Device connection
False = Device connection
status
suspended
True = Device connection OK
Diagnostic events
False = Diagnostic events dis-
enabled
abled
True = Diagnostic events
enabled
Description
Data type: Integer
Access: Read-only
Indicates the operating status of the device
Data type: Integer
Access: Read-only
Indicates the operating status of the device
Data type: Boolean
Access: Read-only
Indicates the status of the device connec-
tion.
Data type: Boolean
Access: No limitations
Enables/disables diagnostic events
67

Advertisement

Table of Contents
loading

Table of Contents