Interoperability List For Iec104 Opc Server; Appendix 1 - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

1MRS758690
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual

Appendix 1

Interoperability list for IEC104 OPC Server

Not supported
Supported
Supported, may need additional engineering
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular tele control systems. Certain parameter values,
such as the choice of "structured" or "unstructured" fields of the Information Object
Address (IOA) of ASDUs represent mutually exclusive alternatives. This means that
only one value of the defined parameters is admitted per system. Other parameters, such
as the listed set of different process information types in command and in monitor direc-
tion allow the specification of the complete set or subsets, as appropriate for the applic-
ations. This clause summarizes the parameters of the previous clauses to facilitate a
suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers, it is necessary that all partners agree on the
selected parameters.
The interoperability list is defined as in the IEC 60870-5-104 protocol and extended with
parameters used in this standard. The text descriptions of parameters which are not
applicable to this companion standard are struck out (the corresponding check box is
marked black).
The full specification of a system can require individual
selection of certain parameters for certain parts of the system,
for example, individual selection of scaling factors for indi-
vidually addressable measured values.
Application layer telegram formats
Function or ASDU is not used
Function or ASDU is used as standardized (default)
Function or ASDU is used in reverse mode
Function or ASDU is used in standard and reverse mode
Function or ASDU can need some additional application level work
131