Integer Controlled Step Position Information (Isc) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.17.6.
52
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
SBO with Normal Security:
ctlVal: MMS Write.request to Oper structure with value.
IEC 61850 OPC Server will do the select before operate.
Direct Control with Enhanced Security:
ctlVal: MMS Write.request to Oper structure with value.
SBO with Enhanced Security:
ctlVal: MMS Write.request to Oper structure with value.
IEC 61850 OPC Server will do the select before operate.

Integer controlled step position information (ISC)

The following table defines the common data class of integer controlled step position
information.
Table 3.2.17.6-1 Integer controlled step position information (ISC)
Name
Type
lastApplError
ApplicationErr-
orCode
ctlVal
INT8
operTm
TimeStamp
orCat
ENUMER-
ATED
orIdent
OCTET
STRING64
ctlNum
INT8U
valWTr.posVal
INT8
val-
BOOLEAN
WTr.transInd
q
Quality
t
TimeStamp
stSeld
BOOLEAN
FC
Value/ Value
range
Refer to
3.2.22, Applica-
tion error
codes
CO
-64 ... 63
CO
not-supported
| bay-control |
station-control
| remote-con-
trol | auto-
matic-bay |
automatic-sta-
tion | auto-
matic-remote |
maintenance |
process
CO, ST
0..255
ST
ST
ST
ST
ST
FALSE |
TRUE
1MRS758690
M/O
OPC Data
Type
VT_I4
M
VT_I4
O
VT_DATE
O
VT_I4
O
VT_BSTR
O
VT_I4
M
VT_I4
M
VT_BOOL
M
VT_I4
M
VT_DATE
O
VT_BOOL

Advertisement

Table of Contents
loading

Table of Contents