ABB COM600 series 5.0 Technical Reference Manual page 144

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

144
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Test procedure (object-specific parameter)
Test procedure
File transfer (station-specific parameter)
File transfer in monitor direction
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analogue values
File transfer in control direction
Transparent file
Background scan (station-specific parameter)
Background scan
Acquisition of transmission delay (station-specific parameter)
Acquisition of transmission delay
Definition of time-outs
Parameter
Default-value
t
0
t
1
t
2
t
3
Remarks
30 s
Time-out of connection establishment
15 s
Time-out of send or test APDUs
10 s
Time-out for acknowledges in case of
no data messages t2 < t1
20
Time-out for sending test frames in
case of a long idle state
1MRS758690
Selected value
1 - 255 s
1 - 255 s
1 - 255 s
1 - 255 s