Controllable Integer Status (Inc); Controllable Enumerated Status (Enc) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

1MRS758690
Name
Type
ctlSelOn
ctlSelOff
stVal
ENUMERATED
q
Quality
t
TimeStamp
ctlCan
BOOLEAN
stSeld
BOOLEAN
4.2.15.
Name
Type
ctlVal
INTEGER
stVal
INTEGER
q
Quality
t
TimeStamp
d
Description
4.2.16.
Name
Type
ctlVal
ENUMERATED
stVal
ENUMERATED
q
Quality
t
Timestamp
d
Description
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Value/ Value
range
FALSE | TRUE
FALSE | TRUE
intermediate-state
(0)
off (1)
on (2)
bad-state (3)
FALSE | TRUE
FALSE | TRUE

Controllable integer status (INC)

Value/ Value
range
Text

Controllable Enumerated Status (ENC)

ENC represents DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1, M_ME_NB_1,
M_ME_TB_1, C_SE_NA, C_SE_NB_1.
Value/ Value
range
Text
Mandat-
Protocol informa-
ory/Optional
tion element
O
SCO
O
SCO
M
DPI
M
BL, SB, NT, IV
M
CP24TIME2A
O
SCO
O
SPI
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA
M
VAI32
M
BL, SB, NT, IV
M
CP24TIME2A
O
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA
M
VAI32
M
BT, SB, NT, IV
M
CP24Time2a
O
OPC data types
VT_BOOL
VT_BOOL
VT_I4
VT_I4
VT_DATE
VT_BOOL
VT_BOOL
OPC data types
VT_I4
VT_I4
VT_I4
VT_DATE
VT_BSTR
OPC data types
VT_I4
VT_I4
VT_I4
VT_DATE
VT_BSTR