Step Position With Transient Indication (Valwithtrans); Pulse Configuration (Pulseconfig); Originator - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.8.
3.2.9.
3.2.10.
28
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Name
Type
max
AnalogueValue
hhLim, hLim, lLim, llLim: These attributes are configuration parameters used in the
context with the range attribute.
min: The min (minimum) attribute represents the minimum process measurement for
which values of i or f are considered within process limits.
max: The max (maximum) attribute represents the maximum process measurement for
which values of i or f are considered within process limits.

Step position with transient indication (ValWithTrans)

The following table defines the mapping of Step position with transient indication
(ValWithTrans).
Table 3.2.8-1 Step position with transient indication (ValWithTrans)
Name
Type
posVal
INT8
transInd
BOOLEAN

Pulse configuration (PulseConfig)

The table following table defines the mapping of pulse configuration (PulseConfig).
Table 3.2.9-1 Pulse configuration (PulseConfig)
Name
Type
cmdQual
ENUMERATED
onDur
INT32U
offDur
INT32U
numPls
INT32U

Originator

The following table defines the mapping of originator (Originator).
Value/ Value
M/O/C
range
floating point
value
Value/ Value
M/O/C
range
-64 ... 63
TRUE | FALSE
Value/ Value
M/O/C
range
pulse(0) | persist-
ent(1)
1MRS758690
OPC Data Type
M
VT_R4
OPC Data Type
M
VT_I4
M
VT_BOOL
OPC Data Type
M
VT_I4
M
VT_I4
M
VT_I4
M
VT_I4