Controllable Double Point (Dpc) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.17.2.
44
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
SBO with Enhanced Security:
ctlVal: MMS Write.request to ctlVal with value. IEC 61850 OPC Server will do the
select before operate.

Controllable double point (DPC)

The following table defines the common data class of controllable double point.
Table 3.2.17.2-1 Controllable double point (DPC)
Name
Type
ctlSelOn
AbbCommand-
Bitmask
ctlSelOff
AbbCommand-
Bitmask
ctlOperOn
AbbCommand-
Bitmask
ctlOperOff
AbbCommand-
Bitmask
ctlCan
AbbCommand-
Bitmask
ctlOper
AbbCommand-
Bitmask
lastApplError
ApplicationErr-
orCode
ctlVal
BOOLEAN
operTm
TimeStamp
origin
Originator
ctlNum
INT8U
stVal
CODED
ENUM
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
FC
Value/ Value
range
Refer to
3.2.22, Applica-
tion error
codes
CO
off (FALSE) |
on (TRUE)
CO
CO, ST
CO, ST
0..255
ST
intermediate-
state (0) | off
(1) | on (2) |
bad-state (3)
ST
ST
ST
FALSE |
TRUE
SV
1MRS758690
M/O
OPC Data
Type
M
VT_I4
M
VT_I4
M
VT_I4
M
VT_I4
M
VT_I4
M
VT_I4
VT_I4
M
VT_BOOL
O
VT_DATE
O
O
VT_I4
M
VT_I1
M
VT_I4
M
VT_DATE
O
VT_BOOL
O
VT_BOOL