Common Data Class Specifications For Controllable Analogue Information; Analog Set Point (Apc) - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.2.18.
3.2.18.1.
54
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
SBO with Normal Security:
ctlVal: MMS Write.request to Oper structure with value.
IEC 61850 OPC Server will do the select before operate.
Direct Control with Enhanced Security:
ctlVal: MMS Write.request to Oper structure with value.
SBO with Enhanced Security:
ctlVal: MMS Write.request to Oper structure with value.
IEC 61850 OPC Server will do the select before operate.
Common data class specifications for controllable analogue
information

Analog set point (APC)

Table 3.2.18.1-1 Analogue set point (APC)
Name
Type
lastApplError
ApplicationErr-
orCode
ctlVal
Analogue-
Value
operTm
TimeStamp
orCat
ENUMER-
ATED
orIdent
OCTET
STRING64
ctlNum
INT8U
mxVal
Analogue-
Value
q
Quality
t
Timestamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
INT32
subQ
Quality
FC
Value/ Value
range
Refer to
3.2.22, Applica-
tion error
codes Applica-
tion error
codes
CO
CO
MX
0..255
MX
MX
MX
MX
FALSE|TRUE
SV
SV
SV
1MRS758690
M/O
OPC Data
Type
VT_I4
M
VT_R4
O
VT_DATE
O
VT_I4
O
VT_BSTR
O
VT_I4
M
VT_R4
M
VT_I4
M
VT_I4
O
VT_BOOL
O
VT_BOOL
O
VT_I4
O
VT_I4

Advertisement

Table of Contents
loading

Table of Contents