Acsi Conformance Statement; General Information About Acsi Conformance Statement - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

1MRS758690
3.5.
3.5.1.
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
The failure status code indicates a failure in requested service. The failure status code
can also include a more detailed error code indicating the failure type, which can be local
or remote failure (see Table 3.4.4-3).
Table 3.4.4-3 Failure
9000
Unspecified error
9100
Remote file open error
9120
Remote file read error
9140
Remote file close error
9200
Remote directory details error
9300
Remote directory details error
9400
Remote file rename error
9500
Error in remote obtaining local file
9520
Error in remote opening local file
9540
Error in remote reading local file
9560
Error in remote closing local file
9600
Remote file delete error
Table 3.4.4-4 Failure details
0
No error details
1
Service parameters error (user error)
Reason: required name attribute is empty
Recovery: check the attribute values and try again
2
Local service error (IEC 61850 OPC Server internal error)
Reason: not connected, too much network traffic, and so on
Recovery: check connection and try again
3
Remote service error (remote device error)
Reason: remote device is not supporting service, wrong parameters, no such file, con-
nection failed, and so on
Recovery: check remote device services support, check parameters (file names), check
connection and try again

ACSI conformance statement

General information about ACSI conformance statement

This section defines the compliance to IEC 61850 in terms of service, modeling, and
engineering interfaces and gives detailed explanation of IEC 61850 capabilities of a
81