File Transfer Service Codes - ABB COM600 series 5.0 Technical Reference Manual

Substation management unit/master protocols (ethernet) and applications
Hide thumbs Also See for COM600 series 5.0:
Table of Contents

Advertisement

3.4.4.
80
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Control code: 0

File Transfer service codes

Status codes can be read from the Status attribute. The status indicates the current service
status and the service result.
Table 3.4.4-1 Service control codes
0
Cancel
1
GetFile
2
GetFileAttributeValues
3
GetFileAttributeValuesEx
4
Rename File
5
SetFile
6
DeleteFile
In the service status codes, the first number indicates success (1) or failure (9). The
second number indicates currently requested service (0 - 6). If a local service is requested
in multiple parts for the remote device, the third number indicates the currently called
remote service (1 - 3). The fourth number gives a detailed failure code (0 - 3).
Example:
9601 = parameters error, remote file delete error
9123 = remote service error, remote file read error
Table 3.4.4-2 Success
1000
Ready
1100
Opening remote file
1120
Reading remote file
1140
Closing remote file
1200
Requesting remote directory file details
1300
Requesting remote directory file details
1400
Renaming remote file
1500
Requesting remote device to obtain local file
1520
Remote device requested to open local file
1540
Remote device requested to read local file
1560
Remote device requested to close local file
1600
Deleting remote file
1000
Service done
1MRS758690

Advertisement

Table of Contents
loading