Equipment Connections; Protection Class 1 Equipment Requirements - GE MiCOM P747 Agile Technical Manual

Busbar protection ied
Table of Contents

Advertisement

Chapter 2 - Safety Information
Caution:
Auxiliary supply wiring and digital input circuits should be protected by a high
rupture capacity NIT or TIA fuse with maximum rating of 16 A. for safety
reasons, current transformer circuits must never be fused. Other circuits should
be appropriately fused to protect the wire used.
4.5

EQUIPMENT CONNECTIONS

Warning:
Terminals exposed during installation, commissioning and maintenance may
present a hazardous voltage unless the equipment is electrically isolated.
Caution:
Tighten M4 clamping screws of heavy duty terminal block connectors to a
nominal torque of 1.3 Nm.
Tighten captive screws of terminal blocks to 0.5 Nm minimum and 0.6 Nm
maximum.
Caution:
Always use insulated crimp terminations for voltage and current connections.
Caution:
Always use the correct crimp terminal and tool according to the wire size.
Caution:
Watchdog (self-monitoring) contacts are provided to indicate the health of the
device on some products. We strongly recommend that you hard wire these
contacts into the substation's automation system, for alarm purposes.
4.6

PROTECTION CLASS 1 EQUIPMENT REQUIREMENTS

Caution:
Earth the equipment with the supplied PCT (Protective Conductor Terminal).
Caution:
Do not remove the PCT.
Caution:
The PCT is sometimes used to terminate cable screens. Always check the PCT's
integrity after adding or removing such earth connections.
18
MiCOM P747
P747-TM-EN-1
P747-TM-EN-1.1