Setting Group Selection; Control Inputs - GE MiCOM P747 Agile Technical Manual

Busbar protection ied
Table of Contents

Advertisement

MiCOM P747
The functions available for direct access using these keys are:

Setting group selection

Control Inputs

CB Control functions
The availability of these functions is controlled by the Direct Access cell in the CONFIGURATION column.
There are four options: Disabled, Enabled, CB Ctrl only and Hotkey only.
For the Setting Group selection and Control inputs, this cell must be set to either Enabled or Hotkey
only. For CB Control functions, the cell must be set to Enabled or CB Ctrl only.
2.9.1
SETTING GROUP SELECTION
By default, only Setting group 1 is enabled. Other setting groups will only be available if they are first
enabled. To be able to select a different setting group, you must first enable them in the CONFIGURATION
column.
To access the hotkey menu from the default display, you press the key directly below the HOTKEY text on
the LCD. The following screen will appear.
Use the right cursor keys to enter the SETTING GROUP menu.
Select the setting group with Nxt Grp and confirm by pressing Select. If neither of the cursor keys is pressed
within 20 seconds of entering a hotkey sub menu, the device reverts to the default display.
2.9.2
CONTROL INPUTS
The control inputs are user-assignable functions. You can use the CTRL I/P CONFIG column to configure
the control inputs for the hotkey menu. In order to do this, use the first setting Hotkey Enabled cell to enable
or disable any of the 32 control inputs. You can then set each control input to latched or pulsed and set its
command to On/Off, Set/Reset, In/Out, or Enabled/Disabled.
By default, the hotkey is enabled for all 32 control inputs and they are set to Set/Reset and are Latched.
To access the hotkey menu from the default display, you press the key directly below the HOTKEY text on
the LCD. The following screen will appear.
Press the right cursor key twice to get to the first control input, or the left cursor key to get to the last control
input.
P747-TM-EN-1
P747-TM-EN-1.1
¬User32 STG GP®
HOTKEY MENU
EXIT
¬Menu User01®
SETTING GROUP 1
Nxt Grp Select
¬User32 STG GP®
HOTKEY MENU
EXIT
Chapter 4 - Configuration
65