Appendix B - Commissioning Record
N/C Watchdog contacts closed?
N/O Watchdog contacts open?
Measured auxiliary supply
1.5
TESTS WITH PRODUCT ENERGISED
N/C Watchdog contacts open?
N/O Watchdog contacts closed?
LCD contrast setting used
Clock set to local time?
Time maintained when auxiliary supply removed?
Alarm (yellow) LED working?
Out of service (yellow) LED working?
Programmable LEDs working?
All opto-inputs working?
All output relays working?
1.6
COMMUNICATION TESTS
SCADA Communication standard
(Courier, DNP3.0, IEC 61850, IEC 60870, Modbus)
Communications established?
Protocol converter tested?
1.7
CURRENT INPUT TESTS
Current Inputs (if applicable)
Displayed current
Phase CT ratio (if applicable)
Input CT
IA
IB
IC
IN
ISEF (if applicable)
Note:
Reuse the table for each CT tested.
426
Test
General Tests
Communications
Applied Value
Result (mark where appropriate)
Yes / No
Yes / No
..........................V DC / AC
Result (mark where appropriate)
Yes / No
Yes / No
...............................
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Result (mark where appropriate)
Yes / No
Yes / No / N/A
Result (mark where appropriate)
Primary / Secondary
Displayed Value
MiCOM P747
P747-TM-EN-1
P747-TM-EN-1.1