Chapter 7 - SCADA Communications
• Read records (event, fault, disturbance)
• Time Synchronisation
• Change active setting group
11.3
IEC 61850 PROTOCOL
If Read-Only Mode is enabled for the Ethernet interfacing with IEC 61850, the following commands are
blocked at the interface:
●
All controls, including:
▪
Enable/disable protection
▪
Operate Control Inputs
▪
CB operations (Close/Trip, Lock)
▪
Reset LEDs
The following commands are still allowed:
●
Read statuses, measurands
●
Generate reports
●
Extract disturbance records
●
Time synchronisation
●
Change active setting group
11.4
READ-ONLY SETTINGS
The following settings are available for enabling or disabling Read Only Mode.
●
RP1 Read Only
●
RP2 Read Only
●
NIC Read Only (where Ethernet is available)
These settings are not available for MODBUS and DNP3.
11.5
READ-ONLY DDB SIGNALS
The remote read only mode is also available in the PSL using three dedicated DDB signals:
●
RP1 Read Only
●
RP2 Read Only
●
NIC Read Only (where Ethernet is available)
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
230
MiCOM P747
P747-TM-EN-1
P747-TM-EN-1.1