Manual Event Record Extraction; Record Data - GE MiCOM P747 Agile Technical Manual

Busbar protection ied
Table of Contents

Advertisement

Chapter 7 - SCADA Communications
the data has been read, the event record can be marked as having been read by writing a value of '2' to
register 40400.
9.5.2

MANUAL EVENT RECORD EXTRACTION

There are three registers available to manually select stored records and three read-only registers allowing
the number of stored records to be determined.
40100: Select Event
40101: Select Fault
40102: Select Maintenance Record
For each of the above registers a value of 0 represents the most recent stored record. The following
registers can be read to indicate the numbers of the various types of record stored.
30100: Number of stored records
30101: Number of stored fault records
30102: Number of stored maintenance records
Each fault or maintenance record logged causes an event record to be created. If this event record is
selected, the additional registers allowing the fault or maintenance record details will also become populated.
9.5.3

RECORD DATA

The location and format of the registers used to access the record data is the same whether they have been
selected using either automatic or manual extraction.
Event Description
Time and Date
30103
Event Type
30107
Event Value
30108
MODBUS Address
30110
Event Index
30111
Additional Data Present
30112
If a fault record or maintenance record is directly selected using the manual mechanism then the data can be
read from the register ranges specified above. The event record data in registers 30103 to 30111 will not be
available.
It is possible using register 40401(G6 data type) to independently clear the stored relay event/fault and
maintenance records. This register also provides an option to reset the device indications, which has the
same effect on the relay as pressing the clear key within the alarm viewer using the HMI panel menu.
212
MODBUS
Length
Address
4
1
2
1
1
1
See G12 data type description
See G13 data type description
Nature of value depends on event type. This will contain the status as a binary flag
for contact, opto-input, alarm, and protection events.
This indicates the MODBUS register address where the change occurred.
Alarm 30011
Relays 30723
Optos 30725
Protection events – like the relay and opto addresses this will map onto the
MODBUS address of the appropriate DDB status register depending on which bit of
the DDB the change occurred. These will range from 30727 to 30785.
For platform events, fault events and maintenance events the default is 0.
This register will contain the DDB ordinal for protection events or the bit number for
alarm events. The direction of the change will be indicated by the most significant
bit; 1 for 0 – 1 change and 0 for 1 – 0 change.
0 means that there is no additional data.
1 means fault record data can be read from 30113 to 30199 (number of registers
depends on the product).
2 means maintenance record data can be read from 30036 to 30039.
MiCOM P747
Comments
P747-TM-EN-1