Opto-Input Labels - GE MiCOM P747 Agile Technical Manual

Busbar protection ied
Table of Contents

Advertisement

MiCOM P747
Courier Text
Col
This cell sets the nominal voltage for opto-input 31
Opto Input 32
11
This cell sets the nominal voltage for opto-input 32
Opto Input 33
11
This cell sets the nominal voltage for opto-input 33
Opto Input 34
11
This cell sets the nominal voltage for opto-input 34
Opto Input 35
11
This cell sets the nominal voltage for opto-input 35
Opto Input 36
11
This cell sets the nominal voltage for opto-input 36
Opto Input 37
11
This cell sets the nominal voltage for opto-input 37
Opto Input 38
11
This cell sets the nominal voltage for opto-input 38
Opto Input 39
11
This cell sets the nominal voltage for opto-input 39
Opto Input 40
11
This cell sets the nominal voltage for opto-input 40
OptoFilter Ctrl1
11
This setting determines whether the in-built noise filter is off or on for each opto-input.
OptoFilter Ctrl2
11
This setting determines whether the in-built noise filter is off or on for each opto-input.
Characteristic
11
This setting selects the opto-inputs' pick-up and drop-off characteristics.
5.3.2

OPTO-INPUT LABELS

Courier Text
Col
GROUP 1
4A
INPUT LABELS
This column contains settings for the opto-input Labels
Opto Input 1
4A
This setting defines the label for opto-input 1
Opto Input 2
4A
P747-TM-EN-1
P747-TM-EN-1.1
Row
Default Setting
21
48-54V
22
48-54V
23
48-54V
24
48-54V
25
48-54V
26
48-54V
27
48-54V
28
48-54V
29
48-54V
50
0xFFFFFFFF
51
0x000000FF
80
Standard 60%-80%
Row
Default Setting
00
01
L1 Not Used
02
L2 Not Used
Description
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
0 = 24/27V, 1 = 30/34V, 2 = 48/54V, 3 =
110/125V or 4 = 220/250V
Binary flag: 0 = Off, 1 = Energised
Binary flag: 0 = Off, 1 = Energised
0 = Standard 60% to 80% or
1 = 50% to 70%
Description
Chapter 6 - Monitoring and Control
Available Options
Available Options
ASCII text
ASCII text
175

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micom p40 agile

Table of Contents