Overcurrent Ddb Signals - GE MiCOM P747 Agile Technical Manual

Busbar protection ied
Table of Contents

Advertisement

MiCOM P747
Menu Text
I>1 Function
This setting determines the tripping characteristic for the first stage overcurrent element.
I>1 Current Set
This sets the pick-up threshold for the first stage overcurrent element.
I>1 Time Delay
This sets the DT time delay for the first stage overcurrent element.
I>1 TMS
This is the Time Multiplier Setting to adjust the operate time of IEC IDMT curves.
I>1 Time Dial
This is the Time Multiplier Setting to adjust the operate time of IEEE/US IDMT curves.
I>1 K (RI)
This setting defines the TMS constant to adjust the operate time of the RI curve.
I>1 Reset Char
This setting determines the type of Reset characteristic used for the IEEE/US curves.
I>1 tRESET
This setting determines the Reset time for the Definite Time Reset characteristic.
I>2 Function
This setting determines the tripping characteristic for the second stage overcurrent element.
I>2 Current Set
This sets the pick-up threshold for the second stage overcurrent element.
I>2 Time Delay
This sets the DT time delay for the second stage element.
5.3

OVERCURRENT DDB SIGNALS

Ordinal
Signal Name
203
I>1 Timer Block
This DDB signal blocks the first stage overcurrent time delay
204
I>2 Timer Block
This DDB signal blocks the second stage overcurrent time delay
P747-TM-EN-1
P747-TM-EN-1.1
Col
Row
36
D1
IEC S Inverse
36
D3
1.0*I18
36
D4
1
36
D5
1
36
D6
1
36
D7
1
36
D8
DT
36
D9
0
36
DA
Disabled
36
DD
1.0*I18
36
DD
1
Source
Programmable Scheme Logic
Programmable Scheme Logic
Default Setting
Description
Type
Description
PSL Output
PSL Output
Chapter 5 - Protection Functions
Available Options
0 = Disabled
1 = DT (DT)
2 = IEC S Inverse (TMS)
3 = IEC V Inverse (TMS)
4 = IEC E Inverse (TMS)
5 = UK LT Inverse (TMS)
6 = Rectifier (TMS)
7 = RI (K)
8 = IEEE M Inverse (TD)
9 = IEEE V Inverse (TD)
10 = IEEE E Inverse (TD)
11 = US Inverse (TD)
12 = US ST Inverse (TD)
From 0.08*I18 to 4.0*I18 step
0.01*I18
From 0 to 100 step 0.01
From 0.025 to 1.2 step 0.025
From 0.01 to 100 step 0.01
From 0.1 to 10 step 0.05
0 = DT
1 = Inverse
From 0 to 100 step 0.01
0 = Disabled
1 = DT (DT)
From 0.08*I18 to 10.0*I18 step
0.01*I18
From 0 to 100 step 0.01
Response
No response
No response
133

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micom p40 agile

Table of Contents