Chapter 6 - Monitoring and Control
Note:
We recommend that you do not set the triggering contact to latching. This is because if you use a latching contact,
the fault record would not be generated until the contact has been fully reset.
2.2.5

MAINTENANCE EVENTS

Internal failures detected by the self-test procedures are logged as maintenance records. Maintenance
records are special types of standard events.
The event type description shown in the Event Text cell for this type of event is always Maint Recorded.
The Event Value cell also provides a unique binary code.
The IED contains a separate register containing the latest maintenance records. This provides a convenient
way of viewing the latest maintenance records and saves searching through the event log. You access these
fault records using the Select Maint setting.
The maintenance record has a number of extra menu cells relating to the maintenance event. These
parameters are Maint Text, Maint Type and Maint Data. They contain details about the maintenance event
selected with the Select Maint cell.
The possible maintenance records are as follows:
Event Value
Event Text
6
FPGA Health Err
7
IO Card Error
9
Code Verify Fail
14
Software Failure
15
H/W Verify Fail
16
Non Standard
17
Ana. Sample Fail
18
NIC Soft Error
22
PSL Latch Reset
23
Control IP Reset
24
Fn Keys Reset
25
SR Gates Reset
26
System Error
27
Solicited Reboot
28
Unrec'ble Error
29
Lockout Request
30
IO Upgrade Fail
31
Application Fail
32
System Restart
33
Unknown Error
34
FPGA Failure
35
Upgrade Mode Req
36
Invalid MAC Addr
156
There is a Field Programmable Gate Array error
There is an I/O card error
There is a code verification failure
There is a general software failure
There is a hardware verification failure
There is a non-standard error
There is a failure with the analogue signal sampling
There is a Network Interface Card error
A PSL latch has been reset
A control input has been reset
A function key has been reset
An SR gate has been reset
There is a system error
The device has been requested to reboot
There is an unrecoverable internal error. The device will reboot after the maintenance record has been
created
A lockout has been requested. This is generated whenever maintenance access is gained through the
USB port
There has been an I/O upgrade failure. This can be caused by a faulty I/O card, or the boot loader
enable bit on the micro-controller being disabled
An application has failed
Not used
There is an unknown error
The Field Programmable Gate Array has failed
Upgrade mode has been requested. This is generated whenever maintenance access is gained through
the USB port
The device has an invalid MAC address
Description
MiCOM P747
P747-TM-EN-1
P747-TM-EN-1.1