9.6.2

AUTOMATIC EXTRACTION PROCEDURE

There are two methods that can be used for automatically extracting disturbances:
Method 1
Method 1 is simpler and is better at extracting single disturbance records (when the disturbance recorder is
polled regularly).
P747-TM-EN-1
P747-TM-EN-1.1
Start
Get number of
disturbances from
register 3x00800
No
Are there
disturbances?
Extract disturbance data
End
V01003
Chapter 7 - SCADA Communications
Yes
Get oldest disturbance ID
from register 3x00801
Select required disturbance
by writing the ID value of
the required record to
register 4x00250
Get disturbance time stamp
from registers 3x00930 –
3x00933