3.8 AC Current Probe MN193 Probe

When installing probes, face the arrow on the probe in the direction of
the load.
The 5A range of the MN193 is designed to work with secondary current transform-
ers. Best accuracy is available when entering the transformer ratio (e.g. 1000/5A).
When used to measure 5A direct, the resolution will be limited to 0.1A max.
Nominal Range: 5A and 100A
Measurement Range:
5A: 0.005A to 6A
100A: 0.1A to 120A
Currents < (Primary x 5) ÷ (Secondary x 1000) or < 250mA on the 5A range
and <0.2A on the 100A range will be displayed as zero with this probe. Power
calculations will also be zeroed when the current is zeroed.
Probe Output Signal: 5A: 200mV/A
Maximum Clamping Diameter: 0.8" (20mm)
Safety: NF EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
Reference Conditions:
Ambient temperature
Humidity
Frequency
Distortion factor
Magnetic field of external origin
Accuracy Specifications:
Range: 10mV/A (1V @ 100Arms)
Primary current (in A
Accuracy (% of the output signal)
Phase shift (°)
Overload: 120A continuous
Range: 200mV/A (1V @ 5Arms) with ratio 1000/5 selected
Primary current (in A
Probe output
Accuracy (% of the output signal)
Phase shift (°)
Overload: 12A continuous
Power Quality Analyzer Model 3945-B
AC
max (1A to 1200A with ratio 1000/5 selected)
AC
max
AC
)
AC
)
AC
(3945-B accuracy included)
100A: 10mV/A
AC;
73°F (23°C) ± 5°F (3°C)
20 to 75% of RH
<1% without superimposed DC current
< 40 A/m (earth's magnetic field)
0.1A to 1A
≤1% ± 2cts
≤1.5°
1 to 10A
10 to 100A
5 to 50mA
0.05 to 0.5A
≤1.5% ± 1ct
≤1.5% ± 1ct
≤1.7°
AC
48 to 65Hz
1A to 120A
≤1% ± 1ct
≤1°
100 to 1200A
0.5 to 6A
≤1% ± 1ct
≤1°
≤1°