User's Manual
Using WESMAINT,
Procedure:
Connect to the
WESMAINT
Step
1
2
D25 Hardware Setup
3
4
5
6
Note
The D25 automatically boots as soon as the power is turned on.
If the D25 fails to function, it might have sustained internal damage during
shipping. Contact GE Grid Solutions for assistance.
84
Continued
WESMAINT
CONNECTOR
Connect a WESMAINT II+ cable to the female DB-9
WESMAINT II+ port on the front panel of the D25.
Attach the other end of the WESMAINT II+ cable to the selected
serial communications port of the PC or terminal.
Move the CONTROLS switch on the front panel of the D25 to the
REMOTE position.
Verify that power cable is properly connected to the D25, and the
proper power is available.
See Power Supply above.
Locate the power switch on the back of the D25, and toggle it to
the ON position.
Results: The POWER indicator, a green LED on the front panel
lights when power to the D25 is turned on.
Monitor the terminal display.
Results: A series of text scripts display as the POST routines are
performed. If the text does not display, check
connections and repeat this procedure.