D25
User's Manual
Control Outputs,
The 32 digital outputs can be configured as four groups of four Raise/Lower
D25KE DB-25
pairs.
Raise/Lower
Note:
Configuration
P1 connections
Use jumper wires on the Control Function Terminal block to configure:
for
Group 1:
Raise/Lower
connect between +VC (P1-5) and JMP1 (P1-3)
Group 2:
connect between +VC (P1-5) and JMP2 (P1-4)
Group 3:
connect between +VC (P1-5) and JMP3 (P1-7)
Group 4:
connect between +VC (P1-5) and JMP4 (P1-8)
Raise/Lower Digital Outputs are numbered in the reverse order: Lower point
Note
#1 is Digital Output point #32
The D25KE module requires two WESTERM KI interposing relay panels to
Raise/Lower
Connections to
support 16 pairs of Raise/Lower digital outputs. To configure and connect
Interposing
the digital outputs:
Relay Panels
Connect a DB-25 cable from J3 of the D25KE to J1 of the first WESTERM KI
interposing relay panel.
Connect another DB-25 cable from J6 of the D25KE to J1 of the second
WESTERM KI interposing relay panel.
Connect a Control Voltage Return connection from the D25KE's P1-2 to each of
the D20 KI's TB9-1
Set both WESTERM KI's Jumpers Z2 – 9 to 2 - 3
50
Continued
The (external) control voltage can be up to 75 Vdc or 50 Vac, at 2 A
maximum.
P1
1
2
Control
Voltage
Control
Voltage
Return
994-0081-3.00-21
3
4
5
6
7
R/L 12 - 9
R/L 8 - 5
R/L 16 - 13
R/L 4 - 1