GE D25 User Manual page 45

Substation controller
Table of Contents

Advertisement

GE Grid Solutions
Control Outputs,
Table: D25KE
Phoenix 8-pin terminal block – P1 Pinout:
DB-25 Control
Function
Terminal
Block – P1
P1
Pin
1
2
3
4
5
6
7
8
GE Information
Continued
Signal
Function
COIL_SUP
Control Voltage
COIL_SUP_R
Control Voltage return
TN
JMP1
Relays 1-8 mode
jumper point
JMP2
Relays 9-16 mode
jumper point
+VC
Control Voltage (fused)
MT
Master Trip Bus
JMP3
Relays 17-24 mode
jumper point
JMP4
Relays 25-32 mode
jumper point
1 2 3 4 5 6 7 8
Interposer Relay Coil Power Supply
connections
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
Jumper to JMP1 through 4 for R/L
Jumper to JMP1 through 4 for T/C
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
Jumper to Pin 1-5 (+VC) for R/L
Jumper to Pin 1-6 (MT) for T/C
994-0081-3.00-21
D25
User's Manual