Downloading a Configuration,
Prerequisites
The following must be available before a FLASH code file can be loaded into
for Serial Code
a D25's FLASH memory:
Download
Windows PC with terminal emulation communication software loaded.
The code file, in the Motorola S-record format, located on a local hard drive. If
the file is located on a network or floppy drive, the download may be
significantly slower.
A WESMAINT cable to connect the PC to the D25's WESMAINT port.
This procedure will suspend all operation of the D25, and following the
Before Starting
download, the unit will probably require a configuration download before it
becomes operational.
Consult your System Administrator for access and authorization to perform
system download procedures.
In Application Monitor, (i.e., when the D25A> prompt is displayed)
configuration files can be downloaded — but code cannot be downloaded.
To download code, System Monitor (i.e., when the D25S> prompt is displayed)
must be running.
Procedure:
Steps to download a firmware file to the D25's FLASH memory
Download files
Step
1
2
Note
If the D25 has no code file loaded, or it has detected a corrupt FLASH file,
you will have to go directly to Step 8 and log directly into the monitor.
GE Information
Continued
This file typically will be named either:
down.shx, or
salxxxx.shx
Access Application Monitor
Connect the WESMAINT serial cable from PC to the D25's
WESMAINT port
Start terminal emulation communication software on the PC, and
configure it as follows:
9600 Bps
8 bit
no parity
VT100 emulation
Xon/Xoff (software) flow control enabled
Action
994-0081-3.00-21
D25
User's Manual
101