GE D25 User Manual page 120

Substation controller
Table of Contents

Advertisement

D25
User's Manual
Main Board,
Continued
Low-Voltage
Jumpers for wetting selection are located on the right edge of the D25 Type
Digital Input
III Main Board.
Card Wetting
Type III
When using low voltage digital input cards, the choice of external wetting
WESDAC:
supply source or voltage-detect input may be made using jumpers JP3 to JP5.
Low Voltage
To use external wetting supply:
Digital Input
Connect external wetting supply to pins 1 and 2 on Connector A, C and/or E
Wetting
Selection
Table:
Type III WESDAC board wetting for backward compatibility with the
Backward
following digital input cards: 517-0402, 517-0403, 517-0425, 517-0426, 517-
Compatibility
0427, 517-0464, 517-0432, and 517-0433.
Jumper
Settings
Digital Input
120
External & Supplied
Wetting
1 to 32
JP5-3 to 5
JP5-4 to 6
32 to 64
JP4-3 to 5
JP4-4 to 6
65 to 96
JP3-3 to 5
JP3-4 to 6
994-0081-3.00-21
GE Grid Solutions
JP5
JP4
JP3
Voltage Detect
JP5-3 to 4
JP4-3 to 4
JP3-3 to 4