Control Outputs,
D25KE FACE-
Trip/Close and Raise/Lower digital outputs can be used on the same D25KE
40 Combined
FACE-40 unit.
R/L and T/C
When assigning raise/lower groups, always start with group 4, then group 3,
and lastly group 2.
Remember that raise/lower points number in the reverse direction from other
point types: point 32 will become lower point 1.
Configuring raise/lower groups with numbers lower than the trip/close group
Note
numbers, or between trip/close groups can result in a very complex and
confusing wiring scheme.
G1 and G2
Jumpering is required to configure a D25KE FACE-40 module for 3 groups
Connections
of trip/close, and one group of raise/lower:
for: 3 Groups
Use jumper wires on the FACE-40 terminal block G1 to configure groups 1
of Trip/Close,
and 2.
and One Group
of Raise/Lower
Group 1:
Group 2:
G1
Use jumper wires on the FACE-40 terminal block G2 to configure groups 3
and 4.
Group 3 for trip/close:
Group 4 for raise/lower:
GE Information
Continued
connect between MTA (G1-39) and JMP1 (G1-37)
connect between MTA (G1-40) and JMP2 (G1-38)
1
3
5
7
9
11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2
4
6
8
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
connect between MTB (G2-5) and JMP3 (G2-3)
connect between VCB (G2-2) and JMP4 (G2-4)
1
3
5
7
9
11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2
4
6
8
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
994-0081-3.00-21
D25
User's Manual
G2
59