Testing Hardware I/O Points - GE D25 User Manual

Substation controller
Table of Contents

Advertisement

GE Grid Solutions

Testing Hardware I/O Points

Testing
To test I/O points:
Hardware I/O
Login to WESMAINT
Points
Navigate to the specific WESMAINT display for the type of points you want to
test
Follow the instructions given below for testing specific types of points
!
The Plant I/O software application version in the D25's firmware determines
the quantity and relative position of data points in the System Point Database
The actual point number that you want to test can be determined by:
Data Points
Viewing the point descriptions that are displayed in WESMAINT
Referring to the SGConfig configuration tables for this specific D25.
Note:
Procedure:
When the POST is complete, login to WESMAINT to test I/O points.
Login to
WESMAINT
Step
1
2
3
4
User name and password shown are factory defaults. If you cannot log in,
WESMAINT
contact your system administrator to obtain new user name and password.
Tips
To select an option from the menus, use the up and down arrow keys to highlight
and item and press
Press
For further information, see the WESMAINT II+ User's Guide
GE Information
Actual point descriptions displayed in WESMAINT depend on
changes made to the point descriptions in the running configuration
file.
Press
on the PC keyboard
ENTER
Results: The Welcome screen appears, including a Login prompt.
Note:
If the Welcome banner does not appear, and only a
<D25S prompt is displayed, a valid code and/or
configuration file is not loaded into the D25's memory.
Stop this procedure and review procedures for restoring
files: see D25 Software.
Type the User Name: westronic and Press
Type the Password: rd and Press
Results: The WESMAINT II+ Main Menu appears.
If a time-out occurs, press
E
, or type the menu item number.
NTER
C
+L
at any time to log out of WESMAINT II+.
TRL
994-0081-3.00-21
Action
. (*)
ENTER
. (*)
ENTER
again, to return to login prompt.
ENTER
D25
User's Manual
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents