Testing Hardware I/O Points,
Note
Only points used by the Plant I/O, based on downloaded configuration, will
display values.
Unused points will be off-line.
Table:
Use this table as example references for the AC analog input verification test.
Reference
Note:
Values
Voltage Phase A Circuit 1
Voltage Phase B Circuit 1
Voltage Phase C Circuit 1
Current Phase A Circuit 1
Current Phase B Circuit 1
Current Phase C Circuit 1
Neutral Current Circuit 1
Voltage Phase A-B Circuit 2
Voltage Phase B-C Circuit 2
Current Phase A-B Circuit 2
Current Phase B-C Circuit 2
Neutral Current Circuit 2
Notes
Full-scale for all AC analog values displayed in WESMAINT is represented by a
count of 32767 (15-bit plus sign value).
Full-scale of voltage measurements is 2.5 times the nominal value.
Full-scale of current measurements is 16 times the nominal value.
For more detailed information, refer to the D25 Plant I/O Subsystem
Configuration Guide.
92
Continued
Nominal values can be determined by reviewing SGConfig's P097
Plant I/O configuration tables for this device.
Point Description
994-0081-3.00-21
GE Grid Solutions
Nominal Value
13107
13107
13107
2048
2048
2048
2048
13107
13107
2048
2048
2048