GE D25 User Manual page 70

Substation controller
Table of Contents

Advertisement

D25
User's Manual
Communications Ports,
Table: D25
Pinout of the D25 MAINT DB-9 connector.
MAINT Port
Pinout
Schematic of the cable wiring necessary for 2-Wire RS-485 connection.
2-Wire RS-485
Cable
COM2
The Universal Time Code (UTC) port located on the back panel provides a
connection to a satellite time-code receiver, or equivalent.
Universal Time
The DB-9-F UTC port can be selected for receive-only RS-232 or RS-422
Code (UTC)
interface, using SGConfig.
Port
Supported UTC Port protocols are IRIG-B and Rugby
Communication parameters are determined by the protocol application.
Note
Many IRIG-B receivers are available with modulated and/or unmodulated
output options.
IRIG-B is received on CTS port.
The input to the UTC port must be unmodulated.
If the unmodulated output of the receiver is a coaxial connection, a converter
will be required to interface the D25.
70
Continued
DB-9 Pin
1
2
3
4
5
6
7
8
9
Description
PIN #
N/C
1
Data -
2
Data -
3
N/C
4
Common Ground
5
N/C
6
Data +
7
Data +
8
Earth Ground
9
994-0081-3.00-21
RS-485
N/C
RX-
TX-
N/C
Com GND
N/C
TX+
RX+
EARTH GND
GE Grid Solutions
PIN #
Description
1
N/C
2
Data -
3
Data -
4
N/C
5
Common Ground
6
N/C
7
Data +
8
Data +
9
Earth Ground
GE Information

Hide quick links: