GE D25 User Manual page 87

Substation controller
Table of Contents

Advertisement

GE Grid Solutions
Testing Hardware I/O Points,
Digital Output
Testing Digital Outputs: You can force digital outputs from WESMAINT.
Verification
Test
!
Use caution when testing digital output points that are connected
to external equipment.
This test may damage external devices, such as relays or
Caution!
reclosers, and may injure personnel.
Procedure:
To conduct this test the code and configuration file must be downloaded to
Verify Digital
the D25's FLASH memory.
Output
From the WESMAINT II+ Main Menu:
Step
1
2
3
4
5
6
GE Information
Continued
On the Main Menu, type 1 — System Data Display.
Results: The System Data Menu appears.
On the System Data Menu, type 2 — Digital Output Display.
Results: The point numbers and (optionally) point descriptions
appear on the WESMAINT II+ display.
Use the arrow keys to move up or down to highlight the desired
point number.
Results: The cursor should now be flashing on the specified point
number.
Press
+
when you are ready to force-change the state of the
CTRL
F
digital output point.
Extra Security
At the Password prompt, type control (*) and press
Results: The Digital Output Force Display appears.
Press
+
to change (update) the relay state.
CTRL
U
994-0081-3.00-21
Action
ENTER
D25
User's Manual
.
87