GE Grid Solutions
Electrical Specifications,
Nominal PT input options
Measurement Range
Overload Voltage
Burden
Nominal CT Input Options
Measurement and DFR Range
Thermal Overload
Burden
Nominal CT Input Options
DFR Range
Measurement Range
Thermal Overload
Burden
Operating temp.
LCD Display size
GE Information
Continued
AC Voltage Inputs
63.5 V
69.3 V
110 V
rms
120 V
rms
220 V
rms
0% to 250% of nominal
250% of nominal continuous
350% of nominal for one (1) minute
Less than 0.1 VA
AC Current Inputs (Standard)
1 A
rms
5 A
rms
2% to 1600% of nominal, asymmetrical
4 times nominal current
30 times nominal current
100 times nominal current 1 second
Note:
Refer to the appropriate PRPI for the accuracy
specifications under over-current conditions.
Less than 0.1 VA @ nominal input current
AC Current Inputs (42x Nominal)
1 A
or
rms
5 A
rms
42x nominal
2% to 1600% of nominal, asymmetrical
4 times nominal current
30 times nominal current 10 seconds
100 times nominal current 1 second
Note:
Refer to the appropriate PRPI for the accuracy
specifications under over-current conditions.
Less than 0.1 VA @ nominal input current
LCD Display
-20 to 70 degrees Celsius
2.75" x 7.4"
994-0081-3.00-21
rms
rms
continuous
10 seconds
continuous over-current may affect the
accuracy of the current values.
continuous
continuous over-current may affect the
accuracy of the current values.
D25
User's Manual
155