ABB DCS 500B Description page 15

Software for thyristor power converter
Hide thumbs Also See for DCS 500B:
Table of Contents

Advertisement

Analog Input
AI2
AI3
AI4
AI5
SDCS-IOE-1
AI6
SDCS-IOE-1
DCS 500 Software Description
AIx CONV MODE-parameter selection
1 = -10...+10V
-20...+20mA
2 = 4...20mA, unipolar
3 = Motor temperature measurement
1 x PT100; output scale: °C
4 = 2 x PT100; output scale: °C
5 = 3 x PT100; output scale: °C
6 = PTC; output scale: ohm (Ω)
7 = PTC; output scale: ohm (Ω)
1 = -10...+10V
-20...+20mA
2 = 4...20mA, unipolar
3 = Motor temperature measurement
1 x PT100; output scale: °C
4 = 2 x PT100; output scale: °C
5 = 3 x PT100; output scale: °C
6 = PTC; output scale: ohm (Ω)
1 = -10...+10V
-20...+20mA
2 = 4...20mA, unipolar
3 = Earth fault current measurement
Output scale: A
on
1 = -10...+10V
-20...+20mA
2 = 4...20mA, unipolar
on
1 = -10...+10V
-20...+20mA
2 = 4...20mA, unipolar
Functional Software description
Terminal boards & settings:
CON-2; IOB-3:
----
CON-2: 500Ω connected X3:7-8
IOB-3: S1:5-6 connected
CON-2: 500Ω connected X3:7-8
IOB-3: S1:5-6 connected
IOB-3: S5:3-4 (5 mA), gain=10
IOB-3: S5:3-4 (5 mA), gain =1
IOB-3: S5:3-4 (5 mA), gain =1
IOB-3: S5:1-2 (1.5 mA), gain =1
CON-2: S1:23-24 (+10V source)
CON-2; IOB-3:
----
CON-2: 500Ω connected X3:9-10
IOB-3: S1:7-8 connected
CON-2: 500Ω connected X3:9-10
IOB-3: S1:7-8 connected
IOB-3: S5:3-4 (5 mA), gain=10
IOB-3: S5:3-4 (5 mA), gain =1
IOB-3: S5:3-4 (5 mA), gain =1
IOB-3: S5:1-2 (1.5 mA), gain =1
CON-2: ----
IOB-3: S1:11-12 not connected
S1:13-14 not connected
CON-2: 500Ω connected X4:1-2
IOB-3: S1: 9-10 connected
S1:11-12 not connected
S1:13-14 not connected
CON-2: 500Ω connected X4:1-2
IOB-3: S1: 9-10 connected
S1:11-12 not connected
S1:13-14 not connected
IOB-3: S1:11-12 connected
13-14 connected
9-10 not connected
Connection terminals: X3:11-12
no action
S1:3-4 connected
S1:3-4 connected
no action
S2:3-4 connected
S2:3-4 connected
7