DCS 500 Thyristor Power Converters
for DC Drive Systems
25 to 5150 A
Operating Instructions
DCS 500B / DCF 500B
DCP 500B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 500 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ABB 500

  • Page 1 DCS 500 Thyristor Power Converters for DC Drive Systems 25 to 5150 A Operating Instructions DCS 500B / DCF 500B DCP 500B...
  • Page 2 How the DCS 500 Documentation System works Description of the converter Volume II D DCS 500B Operating Instructions System Description (documentation in hand) including in- DCS 500B 3ADW000066 formation and advise to commission the drive. If three phase DCF 500B field...
  • Page 3: Operating Instructions

    Thyristor Power Converters Series DCS 500B / DCF 500B DCP 500B 25 to 5150 A OPERATING INSTRUCTIONS Code: 3ADW 000 055 R0401 Rev D DCS_OI_E_D.DOC EFFECTIVE: Oct. 30th, 2002 SUPERSEDES:Rev C Sept. 14th, 2001 2002 ABB Automation Products GmbH. All rights reserved.
  • Page 4 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 5: Safety Instructions

    This chapter contains safety instructions which must be complied with during installation, operation and maintenance of the power converters series DCS 500B / DCF 500B or DCP 500B. If these in- structions are not complied with, this may result in injuries (perhaps even with fatal) or in damage to the power converter, the motor and the driven machine.
  • Page 6 Where appropriate, the text printed next to this symbol describes how a risk of this kind may be avoided. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 7 Mains connection EMERGENCY STOP buttons Intended use DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Notes supply information on states requiring particular attention, or indicate that additional information is available on a specific topic. For this purpose, the following symbols are used:...
  • Page 8: Table Of Contents

    3.9 Uploading and Downloading of Parameters (UPLOAD/DOWNLOAD)...3-10 3.10 Setting of the Display Contrast ...3-12 3.11 Full Name of output pins...3-12 3.12 Selecting output pins ...3-13 3.13 Drive Mode ...3-14 3.14 Running the Drive...3-15 Operational Command Keys...3-15 NSTRUCTIONS DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 9 4.4 Fault Signals (F) ... 4-3 4.5 Alarm Signals (A) ... 4-12 4.6 Status Signals ... 4-17 Appendix A - Connection diagrams Connection diagram 1 ...A-1 Connection diagram 2 ...A-2 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Contents...
  • Page 10 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 11: Chapter 1 - Introduction

    Chapter 4 - Signals and Troubleshooting This chapter describes the available signals and possibilities of dis- play with DCS 500B and DCP 500B. As far as fault signals are con- cerned there will be indicated measures (actions) to be taken for troubleshooting.
  • Page 12: Incoming Inspection

    1 - 2 After opening this package, you should check whether it contains the following items: DCS 500B / DCF 500B or DCP 500B thyristor power con- verter in the configuration ordered DCS 500B / DCF 500B or DCP 500B publications...
  • Page 13: Chapter 2 - Start-Up Instructions

    DCF 501B / DCF 502B: Maximally possible output voltage U DCF 501B / DCF 502B: DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 2 - Start-Up Instructions [Only with the SDCS-CON-2 control board & the CDP 312 panel!] Activates German texts on the display ...
  • Page 14 The function which can be set with Parameter 915 (inputs DI7 and DI8 for switching the contactors) will only be operative when the drive has been wired as shown in connection diagram 2. IV A 2 - 2 designation EM STOP designation ON/OFF DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d ), the...
  • Page 15 P 917, then certain operating states (regeneration) may, due to laws of physics, result in the unit fuses tripping, and in extreme cases in thyristor defects. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d X6: 7 ⇒ „1“ signal (K20 in connection example) X6: 7 ⇒...
  • Page 16 Symbol for displaying parameter values or connections Display Symbol for measuring physical variables Measure IV A 2 - 4 e.g. 1204 = 10000 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Assign the value of 10000 to Parameter 1204...
  • Page 17: Preparatory Work

    Check whether auxiliaries, such as motor fans or unit fans, function properly; while doing this, also check for correct direction of rota- tion and voltage level as well! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 2 - Start-Up Instructions...
  • Page 18: Scaling Intra-Unit Signals

    520 = 4 ⇒ Size C4 has been selected Coding for unit type 521 = 1 : Single bridge (2-Q) converter 4 : Double bridge (4-Q) converter ⇒ on rating plate: DCS 502 xxxx Coding for power section (bridge) type IV A 2 - 6 SDCS-IOB-3: ⇒...
  • Page 19 Set this only for units of the DCP 500 series! 517 = Rated power converter current Enter numerical value from rating plate here 518 = 500 V (fixed!); rated power converter voltage Enter numerical value 500 V here 519 = Temperature monitoring of power section Enter value as indicated in the table „Technical Data“...
  • Page 20: Presetting The Field Supply Unit

    Check field current and field voltage by measuring them; if necessary, correct field current with 503. IV A 2 - 8 Panel display: DIODE FIELD EXCIT Continue with Chapter 2.4 Panel display: FEX2 OR FEX3 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 21 First perform the start-up routine for the DCF 501B or DCF 502B field supply unit (Chapter 2.9) and then: continue with Chapter 2.4 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Panel display: FEX2/3 AUTOTUNING Continue with Chapter 2.4...
  • Page 22: Adjusting The Current Controller

    Switch the electronics section's power supply on again! IV A 2 - 10 Do not preset an external reference! Panel display: NO FIELD EXCITER DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d FIELD REMOVAL?
  • Page 23 505 = 2 CAUTION! Please don't forget! 11202 = SAVE MOT1 SET Save the altered values in the non-volatile memory! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Do not preset an external reference! Panel display: ARM. AUTOTUNING - signal (2201) ⇒...
  • Page 24: Speed Feedback Balancing

    Use R9, R48 or R2716 to set the tacho voltage to 10 % of the maximum tacho voltage. IV A 2 - 12 EMF SPEED ACT CONSTANT FIELD or X1: 1... 3 or X1: 4 Panel display: TACHO VOLT. +/-10 Panel display: ANALOG TACHO DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 25 Switch OFF power, thus stopping the drive; drive coasts. CAUTION! Please don't forget! 11202 = SAVE MOT1 SET Save the altered values in the non-volatile memory! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Panel display: ENCODER A+-, B+-...
  • Page 26: Balancing The Field Supply Unit And The E.m.f. Controller

    R9, R48 or R2716. 12516 = 0 Switch OFF power, thus stopping the drive! IV A 2 - 14 Continue with Chapter 2.7 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d ⇒ Section 2.6.1 ⇒ Section 2.6.2 ⇒...
  • Page 27 Switch OFF power, thus stopping the drive! CAUTION! Please don't forget! 11202 = SAVE MOT1 SET Save the altered values in the non-volatile memory! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 2 - Start-Up Instructions EMF, NO FIELD REV Continue with Chapter 2.7...
  • Page 28 D: normal E: slightly overcompensated; when a higher dynamic response is required F: overcompensated; short reset time and a high P-gain IV A 2 - 16 Panel display: FEXC2/3 MAN. TUNIN DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d 11302...
  • Page 29 Note: Measure motor voltage with the U ARM AC signal (change between ACT and PAR). Scaling of 12516: 20000 corresponds to 100 % speed. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Panel display: NOT ACTIVATED EMF, NO FIELD REV...
  • Page 30 This measure serves to provide a greater safety margin for the motor voltage during start-up. IV A 2 - 18 (will later be entered in 1015) (will later be entered in 1014) (will later be entered in 1013) DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 31 Switch OFF power, thus stopping the drive! CAUTION! Please don't forget! 11202 = SAVE MOT1 SET Save the altered values in the non-volatile memory! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 2 - Start-Up Instructions IV A...
  • Page 32: Balancing The Speed Controller, Plus Fine-Balancing The E.m.f. And The Current Contr

    1205 (POT2) ca. 10% greater than speed at field weakening point The following parameters at the e.m.f. controller must be adapted: 1007 = desired response (behaviour) of controller 1008 = desired response (behaviour) of controller. IV A 2 - 20 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 33: Matching The Thyristor Power Converter Unit To The System Conditions Concerned

    2.8 Matching the thyristor power converter unit to the system conditions concerned - Ramp function generator - Binary inputs and outputs - Limit-value messages - Additional functions IV A DCS 500B / DCP 500B Operating Instructions 2 - 21 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 34: Presetting The 3-Phase Field Supply Unit Dcf 50Xb

    DCF field mode, DCF 506 is monitored, FEX-link in use and DCF 500B is node 1 1216 = 10703 digital input 2 used to monitor the motor fan at a DCS 500B is now used to monitor the DCF 506 overvoltage protection...
  • Page 35 - using the armature converter´s input / outputs Make sure the Emergency Stop Function mentioned at the Make sure, no reference is active (DCS 500B not switched on) 1215 = 2 current controller set to STAND ALONE for high inductive load Switch ON power.
  • Page 36 Save the altered values in the non-volatile memory! The DCS converter in DCF-mode (parameter 1215=1 or higher) will not accept a start command, if an alarm or fault is still active (an A or F indication on the 7-segment dis- play).
  • Page 37: Chapter 3 - Handling Of Control Panel Cdp 31X

    The Control and Display Panel [Control Panel] is used for parame- ter setting, for feedback value measuring and for drive control with series DCS 500B / DCF 500B and DCP 500B thyristor power con- verters. This device is available in different versions depending on the type of unit and software to be used: Units with software S 21.1xx...
  • Page 38: Start Mode

    Action: Disconnect the CDP 31x drive. By this means the the Start Mode another time! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d DCS 500 ID-NUMBER Display with CDP 312 NO COMMUNICATION [x] The CDP is not active for 10 s...
  • Page 39: Panel Functions

    3.3 Panel Functions Actual Signal Display Mode DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x The CDP 31x has four different keypad modes: Actual Signal Display Mode (ACT) Parameter Mode (PAR)
  • Page 40: Parameter Mode

    Parameter DOWNLOAD from CDP 31x to drive CDP 31x display contrast setting Function Display Statusrow UPLOAD Selectable Functions DOWNLOAD Display contrast CONTRAST adjusting DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d 0.0 rpm 00 0.0 rpm 00 <=<= =>=>...
  • Page 41: Drive Mode

    DCS500 ID=0 CDI 300 link (communication bus) Factory-adjusted (default) values for CDP 310 / CDP 311 with DCS 500 For input / parameter selection, the following applies: • Ignore the two right-hand digits; the remaining digits are the group and to be selected •...
  • Page 42 To cancel the new setting and keep the original value press any key before pressing ENTER. The selected Keypad Mode is entered. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Press key Display after key is pressed 0.0 rpm 00 17 RAMP GENERATOR 01 RAMP.[IN]...
  • Page 43: Saving Of The Parameters To Backup Memory

    3.5 Saving of the Parameters to backup memory Step DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x Function To enter the Parameter Mode Selection Select group 112. While holding the arrow down, only the group name is dis- played.
  • Page 44: Fault Resetting (Reset)

    If EMERGENCY STOP is acti- vated, the control panel will show the following ALARM To enter the Fault History Dis- play To RESET the ALARM DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Press key Display after key is pressed 0.0 rpm 00...
  • Page 45: Fault History Display

    3.8 Fault History Display Step DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x Up to 100 faults are stored time related and displayed together with the time they appeared after electronics supply switched on.
  • Page 46: Uploading And Downloading Of Parameters (Upload/Download)

    . Note: For reasons of safety the DOWNLOAD function will only operate if „LOCAL mode“ of the Control Panel CDP 31x is selected! DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d FPROM = FLASH-PROM DCS 500 RAM = Random Access Memory...
  • Page 47 Step DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x Depending on the drive´s condition and the status of the commis- sioning, UPLOAD has to take place before DOWNLOAD, otherwise a warning may be displayed:...
  • Page 48: Full Name Of Output Pins

    To display the full name of the three actual signals press key and hold To return to the Actual Signal Display Mode release key. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Press key Display after key is pressed 0.0 rpm 00...
  • Page 49: Selecting Output Pins

    3.12 Selecting output pins Step DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x Note for CDP 310 / CDP 311: Newly selected actual signals will be used for display until the elec- tronics power supply is switched OFF.
  • Page 50: Drive Mode

    Stopped, main contactor OFF (open) Ü Running, main contactor ON (closed) Ö Control Panel CDP 31x Alarm or fault signalling effective in the drive DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Press key Display after key is pressed DCS500...
  • Page 51: Operational Command Keys

    Panel Key Running the DC- Drive from the CDP31x DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 3 - Handling of Control Panel CDP 31x Operational commands can be given from the Control Panel CDP31x every time when the status row is displayed. Operational commands include START and STOP of the the drive, controlling the main contactor and adjusting the reference.
  • Page 52: Speed Reference Setting For The Drive

    To change the reference: (slow change) (fast change) To exit the Reference Setting Mode. The selected Keypad Mode is entered. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Press key Display after key is pressed 0.0 rpm 00 SPEED AC 0.0 rpm...
  • Page 53: Chapter 4 - Signals And Troubleshooting

    ⇑ ⇓ In addition to this the DCS 500B DCF 500B or DCP 500 combined with the LCD of the control panel CDP 31x will be able to show the fault and alarm signals as well as the status signals (selected by signal numbers ) as clear text.
  • Page 54: General Messages

    No TC-link board (not valid for software version S21.1xx) Communic. board SDCS-COM-x faulty No control program in memory ASIC not O.K. Parameter FLASH identity test failed DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d – Remark – – –...
  • Page 55: Fault Signals (F)

    CDP 31x display Auxil. undervoltage Overcurrent DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting The fault signals will be shown on the seven segment display of the control board SDCS-CON-x as codes F . . as well as on the LCD of the control panel CDP 31x as clear text.
  • Page 56 Overload of MOTOR 1 Check: - Motor temperature (let motor cool down and restart); - Motor ratings and parameters of thermal model; - Motor sizing or load cycle. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Status Remark signal (FAULT_WORD_1/2) 11103 bit 11 S21.232...
  • Page 57 F 14 Speed meas. fault F 17 Type coding fault F 18 Backup read fault DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Action Actual current changed faster than allowed The rate of current change is monitored.
  • Page 58 4 - 6 Definition / Action No communication between CDP 31x/CMT and DCS 500B / DCF 500B or DCP 500B in lo- cal control mode (LOCAL) Check: - Connection cable between CDP 31x – DCS 500 / DCP 500 (unplug connection cable from CDP 31x and plug in again);...
  • Page 59 Not in synchronism F 31 F 32 Field ex.1 overcurr F 33 Field ex.1 comerror DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Action Armature (DC circuit) overvoltage Check: - Setting of param. [...
  • Page 60 - power supply for the field unit not within permissi- ble limits Reasons for (2): - field supply unit is broken - field reversal took too long time - field current lower than threshold because DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Status signal (FAULT_WORD_1/2) 11102...
  • Page 61 No main cont. ack. F 42 Field ex.1 not OK Field ex.2 not OK F 43 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Action field weakening range too big / threshold...
  • Page 62 - Communication between module and thyristor power con- Nxxx-0x verter O.K.? - Correct setting of the time inter- val between two telegrams via parameter [P 921] DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Status signal (FAULT_WORD_1/2) 11101 bit 7 11101...
  • Page 63 CDP 31x display F 65 Reversal Fault F 66 Current Difference DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Action Reversal of direction of current is not O.K. The reversal of the direction of current was not correct.
  • Page 64: Alarm Signals (A)

    Alarm Current Regulator/Controller blocked Pin 404 (BLOCK) is set to logical "1“. When pin is set to logical "0“, the alarm sig- nal will be reset. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d - will not A 101...
  • Page 65 A 120 Arm.curr.dev.alarm A 121 Ext.Overvolt.Alarm A 123 Motor 2 temp. alarm A 124 Motor 2 overl alarm A 126 Conv.FAN ack.alarm DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Possible source...
  • Page 66 Set 2 (over [ P 913] ) - the content of the [P 11202] RAM been saved over Value 5 (SELECT_MOT2_SET) in Motor Set 2? DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Signal number (ALARM_WORD_1/2) 11104 bit 15 11105...
  • Page 67 A 134 Backup not allowed A 136 Write backup alarm A 137 Arm. current ripple A 138 Init values read A 140 Auto-reclosing DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / Possible source...
  • Page 68 - Switch ON electronics; - Select BACKUPSTOREMODE [11202]; - Save default parameter set; - Switch OFF electronics; - Reset jumper S2 to its original position; - Switch ON electronics again. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Signal Remark number (ALARM_WORD_1/2)
  • Page 69: Status Signals

    CANNOT AUTOTUNE reserved IF AT START ? DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting The status of drive functions (autotuning of controllers; saving val- ues) is shown by status signals named 11201 and 11202. The...
  • Page 70 Status of this mode. This is used to give commands to parameter handling function in the drive Save motor set 1 Save motor set 2 Load factory values Load motor set 1 Load motor set 2 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Remark...
  • Page 71 (FIELD1_REV_ACK (ACK_CSC_ON) (ACK_FEXC_ON (FIELD_REF_ON) (FIELD1_CURR_MIN_L) DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Chapter 4 - Signals and Troubleshooting Definition / explication of the signal Load application; if additional function blocks are ac- tivated and saved via SAVE MOTx SET and modified...
  • Page 72 -------- primary (AC) or secondary (48Vdc) power failure synchronization signal missing pulse firing section not in synchronism not released DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Remark...
  • Page 73: Appendix A - Connection Diagrams

    Connection diagram 1 DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d Appendix A - Connection diagrams For detailed information see System description DCS 500B / DCF 500B. IV A A - 1...
  • Page 74 Appendix A - Connection diagrams Connection diagram 2 IV A A - 2 For detailed information see System description DCS 500B / DCF 500B. DCS 500B / DCP 500B Operating Instructions 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 75 Appendix A - Connection diagrams IV A DCS 500B / DCP 500B Operating Instructions A - 3 3ADW000055R0401_DCS500B_Operating Instruction_e_d...
  • Page 76 ABB Automation Products GmbH Postfach 1180 Lampertheim • GERMANY Tel: +49 (0) 62 06-5 03-0 Fax: +49 (0) 62 06-5 03-6 09 *055R0401A2440000* www.abb.com/dc *055R0401A2440000*...