ABB DCS 500B Description page 133

Software for thyristor power converter
Hide thumbs Also See for DCS 500B:
Table of Contents

Advertisement

PANEL_DISC_MODE
Parameter of DRIVE LOGIC-function block.
Selects the operation when the panel or CMT communication is disconnected during local
operation:
0 = STOP BY RAMP
1 = STOP BY TORQ LIM
2 = STOP BY COASTING
3 = STOP BY DYN.BRAKE
4 = CONTINUE REMOTE
918
FB_P: E2
SC: -
PWR_LOSS_MODE
Parameter of DRIVE LOGIC-function block.
Selects if the auto-reclosing function is used when the power is disconnected for a short
time:
0 = DISABLE
1 = ENABLE
919
FB_P: E2
SC: -
COMFAULT_MODE
Parameter of DRIVE LOGIC-function block.
Specifies the reaction of the drive after occurrance of a communication fault.
When a fieldbus communication module detects a communication fault these reaction
of the DCS 500 can be selected:
0 = STOP BY RAMP
1 = STOP BY TORQ LIM
2 = STOP BY COASTING
3 = NOTHING
920
FB_P: E2
SC: -
COMFAULT_TIMEOUT
Parameter of DRIVE LOGIC-function block.
Sets sets the communication timeout counter.
It can be adjusted in 20 ms steps from
0 = disable fieldbus timeout (F60) supervision
1 =
1 * 20 ms
150 = 150 * 20 ms = 3 sec
921
FB_P: I2
SC: 20
(decelerate with ramp generator)
(decelerate with torque limit)
(make a coast stop)
(use dynamic braking)
(change to remote control)
HL: 4
HL: 1
(decelerate with ramp generator)
(decelerate with torque limit)
(make a coast stop)
(no action)
HL: 3
to
HL: 150
DCS500 Pin and Parameter list
LL: 0
D: 0
LL: 0
D: 0
LL: 0
D: 0
LL: 0
D: 2
( S3/16 )
U: -
( S3/16 )
U: -
( S3/16 )
U: -
( S3/16 )
U: ms
A 29